Ex-Junction box GHG 791

Over view

GHG 791 01 up to 6 terminals
Cable entry/enclosure drilling max. 4 x M25 for cable Ø 10 – 17 mm
max. 4 x M20 metal thread
Connecting terminals 4 x + 1 PE
Dimensions (L x W x H) 81.5 x 100 x 61 mm
Weight approx. 0.3 kg

 

GHG 791 02 up to 8 terminals
Cable entry/enclosure drilling max. 6 x M25 for cable Ø 10 – 17 mm
max. 6 x M32 for cable Ø 12 – 21 mm
max. 6 x M20 metal thread
Connecting terminals 6 x + 2 PE
Dimensions (L x W x H) 117.5 x 113.5 x 73.5 mm
Weight approx. 0.5 kg

Key Feature

GHG 791 01 up to 6 terminals / GHG 791 02 up to 8 terminals

Marking accd. to 94/9/EC II 2 G Ex dem ia II, IIC T6 / II 2 D Ex tD A21 IP66 T80 °C
EC-Type Examination Certificate PTB 00 ATEX 3108
IECEx Certificate of Conformity IECEx BKI 07.0034
Marking accd. to IECEx Ex e II T6 / Ex ia IIC T6
Ex tD A21 IP66 T58 °C
Permissible ambient temperature –20 °C to +40 °C / –55 °C to +40 °C (option)
Rated voltage 690 V / 550 V1)
Rated current depends on terminal cross section
Terminal cross section max. 3 x 4 mm2 or 1 x 10 mm2 with pin cable lug + 1 x 2.5 mm2 fine wire
max. 3 x 6 mm2 or 4 x 4 mm2 solid-wire
Protection class I
Degree of protection accd. to EN 60529 IP66
Enclosure material Polyamide

Price: Call